![ABB Relion REC615 Скачать руководство пользователя страница 35](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253035.webp)
Table 6: Comparison of authority logging levels
Audit trail event
Authority logging level
None
Configura-
tion change
Setting
group
Setting
group,
control
Settings
edit
All
Configuration change
●
●
●
●
●
Firmware change
●
●
●
●
●
Firmware change fail
●
●
●
●
●
Attached to retrofit
test case
●
●
●
●
●
Removed from retro-
fit test case
●
●
●
●
●
Setting group remote
●
●
●
●
Setting group local
●
●
●
●
Control remote
●
●
●
Control local
●
●
●
Test on
●
●
●
Test off
●
●
●
Reset trips
●
●
●
Setting commit
●
●
Time change
●
View audit log
●
Login
●
Logout
●
Password change
●
Firmware reset
●
Violation local
●
Violation remote
●
2.5
Communication
Operational information and controls are available through these protocols.
However, some communication functionality, for example, horizontal
communication between the protection relays, is only enabled by the IEC 61850
communication protocol.
The IEC 61850 communication implementation supports all monitoring and control
functions. Additionally, parameter settings, disturbance recordings and fault
records can be accessed using the IEC 61850 protocol. Disturbance recordings
are available to any Ethernet-based application in the IEC 60255-24 standard
COMTRADE file format. The protection relay can send and receive binary signals
from other devices (so-called horizontal communication) using the IEC 61850-8-1
GOOSE profile, where the highest performance class with a total transmission time
of 3 ms is supported. Furthermore, the protection relay supports sending and
receiving of analog values using GOOSE messaging. The protection relay meets
1MRS758755 C
REC615 and RER615 overview
REC615 & RER615
Technical Manual
35
Содержание Relion REC615
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......