9.3.6.2
SECRSYN Output signals
Table 675: SECRSYN Output signals
Name
Type
Description
SYNC_INPRO
BOOLEAN
Synchronizing in progress
SYNC_OK
BOOLEAN
Systems in synchronism
CL_FAIL_AL
BOOLEAN
CB closing failed
CMD_FAIL_AL
BOOLEAN
CB closing request failed
LLDB
BOOLEAN
Live Line, Dead Bus
LLLB
BOOLEAN
Live Line, Live Bus
DLLB
BOOLEAN
Dead Line, Live Bus
DLDB
BOOLEAN
Dead Line, Dead Bus
9.3.7
Settings
9.3.7.1
SECRSYN Group settings
Table 676: SECRSYN Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Live dead mode
-1=Off
1=Both Dead
2=Live L, Dead B
3=Dead L, Live B
4=Dead Bus, L Any
5=Dead L, Bus Any
6=One Live, Dead
7=Not Both Live
1=Both Dead
Energizing check
mode
Difference voltage
0.01...0.50
xUn
0.01
0.05
Maximum voltage
difference limit
Difference frequen-
cy
0.0002...0.1000
xFn
0.0001
0.0010
Maximum frequen-
cy difference limit
Difference angle
5...90
deg
1
5
Maximum angle
difference limit
Table 677: SECRSYN Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Synchro check
mode
1=Off
2=Synchronous
3=Asynchronous
3=Asynchronous
Synchro check op-
eration mode
Table continues on the next page
1MRS758755 C
Control functions
REC615 & RER615
Technical Manual
653