in the European standard EN 50160. However, the power quality standards like the
international standard IEC 61000-4-30 specify that the voltage variation event is
characterized by its duration and magnitude. Furthermore, IEEE Std 1159-1995 gives
the recommended practice for monitoring the electric power quality.
Voltage variation measurement can be done to the phase-to-earth and phase-
to-phase voltages. The power quality standards do not specify whether the
measurement should be done to phase or phase-to-phase voltages. However, in
some cases it is preferable to use phase-to-earth voltages for measurement. The
measurement mode is always TRMS.
10.3.7
Signals
10.3.7.1
PHQVVR Input signals
Table 712: PHQVVR Input signals
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current mag-
nitude
I_B
SIGNAL
0
Phase B current mag-
nitude
I_C
SIGNAL
0
Phase C current mag-
nitude
U_A
SIGNAL
0
Phase-to-earth volt-
age A
U_B
SIGNAL
0
Phase-to-earth volt-
age B
U_C
SIGNAL
0
Phase-to-earth volt-
age C
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
10.3.7.2
PHQVVR Output signals
Table 713: PHQVVR Output signals
Name
Type
Description
OPERATE
BOOLEAN
Voltage variation detected
START
BOOLEAN
Voltage variation present
SWELLST
BOOLEAN
Voltage swell active
DIPST
BOOLEAN
Voltage dip active
INTST
BOOLEAN
Voltage interruption active
1MRS758755 C
Power quality measurement functions
REC615 & RER615
Technical Manual
721