Protected feeder
Background network
Im(Yo)
Re(Yo)
Reverse fault:
Yo ≈ -j*I
eFd
/U
ph
Figure 166: Admittance calculation during a reverse fault
R
CC
Resistance of the parallel resistor
L
CC
Inductance of the compensation coil
R
n
Resistance of the neutral earthing resistor
Y
Fd
Phase-to-earth admittance of the protected feeder
Y
Bg
Phase-to-earth admittance of the background network
For example, in a 15 kV compensated network with the magnitude of the earth-fault
current in the protected feeder being 10 A (Rf = 0 Ω), the theoretical value for the
measured admittance during an earth fault in the reverse direction, that is, outside
the protected feeder, can be calculated.
Yo
j
I
U
j
A
kV
j
eFd
ph
≈ − ⋅
= − ⋅
= − ⋅
10
15
3
1 15
.
milliSiemens
(Equation 15)
The result is valid regardless of the neutral earthing method.
Protection functions
1MRS758755 C
346
REC615 & RER615
Technical Manual