Parameter
Values (Range)
Unit
Step
Default
Description
Default Var Obj 21
1=1:32bit FrzCnt
2=2:16bit FrzCnt
5=5:32bit FrzCnt&time
6=6:16bit FrzCnt&time
9=9:32bit FrzCnt noflag
10=10:16bit FrzCnt noflag
6=6:16bit FrzCnt&time 1=32 bit frz counter; 2=16
bit frz counter; 5=32 bit
frz counter with time;
6=16 bit frz counter with
time; 9=32 bit frz counter
without flag;10=16 bit frz
counter without flag.
Default Var Obj 22
1=1:32bit Cnt evt
2=2:16bit Cnt evt
5=5:32bit Cnt evt&time
6=6:16bit Cnt evt&time
6=6:16bit Cnt
evt&time
1=32 bit counter event;
2=16 bit counter event;
5=32 bit counter event
with time; 6=16 bit coun-
ter event with time.
Default Var Obj 23
1=1:32bit FrzCnt evt
2=2:16bit FrzCnt evt
5=5:32bit FrzCnt evt&time
6=6:16bit FrzCnt evt&time
6=6:16bit FrzCnt
evt&time
1=32 bit frz counter
event; 2=16 bit frz coun-
ter event; 5=32 bit frz
counter event with time;
6=16 bit frz counter event
with time.
Default Var Obj 30
1=1:32bit AI
2=2:16bit AI
3=3:32bit AI noflag
4=4:16bit AI noflag
5=5:AI float
6=6:AI double
5=5:AI float
1=32 bit AI; 2=16 bit AI;
3=32 bit AI without flag;
4=16 bit AI without flag;
5=AI float; 6=AI double.
Default Var Obj 32
1=1:32bit AI evt
2=2:16bit AI evt
3=3:32bit AI evt&time
4=4:16bit AI evt&time
5=5: float AI evt
6=6:double AI evt
7=7:float AI evt&time
8=8:double AI evt&time
7=7:float AI evt&time
1=32 bit AI event; 2=16
bit AI event; 3=32 bit
AI event with time; 4=16
bit AI event with time;
5=float AI event; 6=dou-
ble AI event; 7=float AI
event with time; 8=dou-
ble AI event with time.
Default Var Obj 40
1=1:32bit AO
2=2:16bit AO
3=3:AO float
4=4:AO double
2=2:16bit AO
1=32 bit AO; 2=16 bit AO;
3=AO float; 4=AO double.
Default Var Obj 42
1=1:32bit AO evt
2=2:16bit AO evt
3=3:32bit AO evt&time
4=4:16bit AO evt&time
5=5:float AO evt
6=6:double AO evt
7=7:float AO evt&time
8=8:double AO evt&time
4=4:16bit AO evt&time 1=32 bit AO event; 2=16
bit AO event; 3=32 bit
AO event with time; 4=16
bit AO event with time;
5=float AO event; 6=dou-
ble AO event; 7=float AO
event with time; 8=dou-
ble AO event with time.
3.1.17
COM1/2 serial communication settings
Basic functions
1MRS758755 C
56
REC615 & RER615
Technical Manual