Table 144: TPGAPC Output signals
Name
Type
Description
OUT1
BOOLEAN
Output 1 status
OUT2
BOOLEAN
Output 2 status
Settings
TPGAPC Non group settings (Basic)
Table 145: TPGAPC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Pulse time
0...60000
ms
1
150
Minimum pulse
time
Technical revision history
Table 146: TPGAPC Technical revision history
Technical revision
Change
B
Outputs now visible in menu
C
Internal improvement
3.17.2.2
Minimum pulse timer TPSGAPC
Function block
Figure 79: Function block
Functionality
The Minimum second pulse timer function TPSGAPC contains two independent
timers. The function has a settable pulse length (in seconds). The timers are used
for setting the minimum pulse length for example, the signal outputs. Once the
input is activated, the output is set for a specific duration using the
Pulse time
setting. Both timers use the same setting parameter.
Figure 80: A = Trip pulse is shorter than Pulse time setting, B = Trip pulse is longer
than Pulse time setting
Basic functions
1MRS758755 C
146
REC615 & RER615
Technical Manual