8.1.8.6
Monitored data
FMMXU Monitored data
Table 617: FMMXU Monitored data
Name
Type
Values (Range)
Unit
Description
f-Hz
FLOAT32
35.00...75.00
Hz
Measured fre-
quency
F_INST
FLOAT32
35.00...75.00
Hz
Frequency, in-
stantaneous val-
ue
F_DB
FLOAT32
35.00...75.00
Hz
Frequency, re-
ported value
F_RANGE
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
Measured fre-
quency range
8.1.8.7
Technical data
Table 618: FMMXU Technical data
Characteristic
Value
Operation accuracy
±10 mHz
(in measurement range 35...75 Hz)
8.1.8.8
Technical revision history
Table 619: FMMXU Technical revision history
Technical revision
Change
B
Added new setting
Def frequency Sel
. Fre-
quency measurement range lowered from 35
Hz to 10 Hz.
8.1.9
Sequence current measurement CSMSQI
8.1.9.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Sequence current measurement
CSMSQI
I1, I2, I0
I1, I2, I0
Measurement functions
1MRS758755 C
594
REC615 & RER615
Technical Manual