![ABB Relion REC615 Скачать руководство пользователя страница 163](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253163.webp)
3.17.10.1
Function block
AI1_VALUE
AI2_VALUE
AO2_VALUE
AI3_VALUE
AI4_VALUE
AO3_VALUE
AO4_VALUE
AO1_VALUE
SCA4GAPC
Figure 95: Function block
3.17.10.2
Functionality
The analog value scaling function SCA4GAPC is used for scaling the analog value. It
allows creating events from analog values.
The analog value received via the
AIn_VALUE
input is scaled with the
Scale ratio n
setting. The scaled value is available on the
AOn_VALUE
output.
Analog input range is from –10000.0 to 10000.0.
Analog output range is from –2000000.0 to 2000000.0.
If the value of the
AIn_VALUE
input exceeds the analog input range,
AOn_VALUE
is set to 0.0.
If the result of
AIn_VALUE
multiplied by the Scale ratio n setting exceeds
the analog output range,
AOn_VALUE
shows the minimum or maximum
value, according to analog value range.
3.17.10.3
Signals
Table 179: SCA4GAPC Input signals
Name
Type
Default
Description
AI1_VALUE
FLOAT32
0.0
Analog input value of
channel 1
AI2_VALUE
FLOAT32
0.0
Analog input value of
channel 2
AI3_VALUE
FLOAT32
0.0
Analog input value of
channel 3
AI4_VALUE
FLOAT32
0.0
Analog input value of
channel 4
1MRS758755 C