![ABB Relion REC615 Скачать руководство пользователя страница 151](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253151.webp)
3.17.4.4
Operation principle
The function can be enabled and disabled with the
Operation setting. The
corresponding parameter values are "On" and "Off".
The operation of DTMGAPC can be described with a module diagram. All the
modules in the diagram are explained in the next sections.
Q
Time
comparator
BLOCK
FREEZE
Figure 86: Functional module diagram
Time comparator
This module compares the current day and time with the respective day activation
hour
xxx Act hour and activation minute xxx Act Min settings. When the time of the
day reaches the set activation time, output
Q is activated. It remains activate for the
duration defined by the setting
xxx Act Dur.
The output remains active until the next day if the setting for
xxx Act Dur
is set such that it results into rollover of the day.
Different activation and deactivation times can be set for all days of the week. The
activation and deactivation can also be disabled for a specific day, for example, if
the activation or deactivation is not needed on Sundays, the
Sunday Act enable can
be set "False".
Activation of the
BLOCK
input deactivates the function output whereas the
activation of
FREEZE
input freezes the output. The
BLOCK
input has always a higher
priority than the
FREEZE
input.
3.17.4.5
Application
The daily timer function is useful in applications that require signal activation and
deactivation at a specific time of the day. Different activation times and duration
can be set for different days of the week. For example, if the signal should be active
on Mondays between 7.15 a.m. and 4 p.m., the
Monday Act enable setting should
be "1=True",
Mon Act hour and Mon Act Mn as "07" for hours and "15" for minutes
respectively and
Mon Act Dur should be "525" minutes. The behavior of output Q is
illustrated in
1MRS758755 C
Basic functions
REC615 & RER615
Technical Manual
151