The
Blocking mode setting has three blocking methods. In the "Freeze timers"
mode, the operation timer is frozen to the prevailing value, but the
OPERATE
output
is not deactivated when blocking is activated. In the "Block all" mode, the whole
function is blocked and the timers are reset. In the "Block OPERATE output" mode,
the function operates normally but the
OPERATE
output is not activated.
4.3.1.5
Application
Since the negative sequence current quantities are not present during normal,
balanced load conditions, the negative sequence overcurrent protection elements
can be set for faster and more sensitive operation than the normal phase-
overcurrent protection for fault conditions occurring between two phases. The
negative sequence overcurrent protection also provides a back-up protection
functionality for the feeder earth-fault protection in solid and low resistance
earthed networks.
The negative sequence overcurrent protection provides the back-up earth-fault
protection on the high voltage side of a delta-wye connected power transformer
for earth faults taking place on the wye-connected low voltage side. If an earth fault
occurs on the wye-connected side of the power transformer, negative sequence
current quantities appear on the delta-connected side of the power transformer.
The most common application for the negative sequence overcurrent protection is
probably rotating machines, where negative sequence current quantities indicate
unbalanced loading conditions (unsymmetrical voltages). Unbalanced loading
normally causes extensive heating of the machine and can result in severe damages
even over a relatively short time period.
Multiple time curves and time multiplier settings are also available for coordinating
with other devices in the system.
4.3.1.6
Signals
Table 412: NSPTOC Input signals
Name
Type
Default
Description
I
2
SIGNAL
0
Negative phase se-
quence current
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
ENA_MULT
BOOLEAN
0=False
Enable signal for cur-
rent multiplier
Table 413: NSPTOC Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
Protection functions
1MRS758755 C
412
REC615 & RER615
Technical Manual
Содержание Relion REC615
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......