6.3.6
Signals
6.3.6.1
MDSOPT Input signals
Table 562: MDSOPT Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0=False
Block input status
POS_ACTIVE
BOOLEAN
0=False
When active indicates
the equipment is run-
ning
RESET
BOOLEAN
0=False
Resets the accumula-
ted operation time to
initial value
6.3.6.2
MDSOPT Output signals
Table 563: MDSOPT Output signals
Name
Type
Description
ALARM
BOOLEAN
Alarm accumulated operation
time exceeds Alarm value
WARNING
BOOLEAN
Warning accumulated opera-
tion time exceeds Warning
value
6.3.7
Settings
6.3.7.1
MDSOPT Non group settings
Table 564: MDSOPT Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Warning value
0...299999
h
1
8000
Warning value for
operation time su-
pervision
Alarm value
0...299999
h
1
10000
Alarm value for op-
eration time super-
vision