14.5
Energizing inputs of SIM0002/SIM0904
Table 755: Energizing inputs of SIM0002/SIM0904
Description
Value
Current sensor in-
put
Rated current voltage (in secon-
dary side)
75 mV...9000 mV
1
Continuous voltage withstand
125 V
Input impedance at 50/60 Hz
2...3 MΩ
2
Voltage sensor in-
put
Rated voltage
6 kV...30 kV
3
Continuous voltage withstand
50 V
Input impedance at 50/60 Hz
3 MΩ
14.6
Binary inputs
Table 756: Binary inputs
Description
Value
Operating range
±20% of the rated voltage
Rated voltage
24...250 V DC
Current drain
1.6...1.9 mA
Power consumption
31.0...570.0 mW
Threshold voltage
16...176 V DC
Reaction time
3 ms
1
Equals the current range of 40...4000 A with a 80 A, 3 mV/Hz Rogowski
2
Depending on the used nominal current (hardware gain)
3
This range is covered (up to 2*rated) with sensor division ratio of 10 000:1