Name
Type
Values (Range)
Unit
Description
ANGLE_RCA
FLOAT32
-180.00...180.00
deg
Angle between
operating angle
and characteris-
tic angle
ANGLE
FLOAT32
-180.00...180.00
deg
Angle between
polarizing and
operating quan-
tity
I_OPER
FLOAT32
0.00...40.00
xIn
Calculated oper-
ating current
FDEFLPDEF
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Table 366: DEFHPDEF Monitored data
Name
Type
Values (Range)
Unit
Description
FAULT_DIR
Enum
0=unknown
1=forward
2=backward
3=both
Detected fault
direction
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start
time / operate
time
DIRECTION
Enum
0=unknown
1=forward
2=backward
3=both
Direction infor-
mation
ANGLE_RCA
FLOAT32
-180.00...180.00
deg
Angle between
operating angle
and characteris-
tic angle
ANGLE
FLOAT32
-180.00...180.00
deg
Angle between
polarizing and
operating quan-
tity
I_OPER
FLOAT32
0.00...40.00
xIn
Calculated oper-
ating current
DEFHPDEF
Enum
1=on
Status
Protection functions
1MRS758755 C
330
REC615 & RER615
Technical Manual
Содержание Relion REC615