![ABB Relion REC615 Скачать руководство пользователя страница 637](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253637.webp)
Table 655: DCXSWI Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation counter
0...10000
1
0
Breaker operation
cycles
Adaptive pulse
0=False
1=True
1=True
Stop in right posi-
tion
Event delay
0...60000
ms
1
10000
Event delay of the
intermediate posi-
tion
Vendor
0
External equipment
vendor
Serial number
0
External equipment
serial number
Model
0
External equipment
model
9.1.8
Monitored data
9.1.8.1
CBXCBR Monitored data
Table 656: CBXCBR Monitored data
Name
Type
Values (Range)
Unit
Description
POSITION
Dbpos
0=intermediate
1=open
2=closed
3=faulty
Apparatus posi-
tion indication
9.1.8.2
DCXSWI Monitored data
Table 657: DCXSWI Monitored data
Name
Type
Values (Range)
Unit
Description
POSITION
Dbpos
0=intermediate
1=open
2=closed
3=faulty
Apparatus posi-
tion indication
1MRS758755 C