Figure 327: Schematic diagram of delayed initiation input signals
In total, the AR function contains six separate initiation lines used for the initiation
or blocking of the autoreclosing shots. These lines are divided into two types of
channels. In three of these channels, the signal to the AR function can be delayed,
whereas the other three channels do not have any delaying capability.
Each channel that is capable of delaying a start signal has four time delays. The time
delay is selected based on the shot pointer in the AR function. For the first reclose
attempt, the first time delay is selected; for the second attempt, the second time
delay and so on. For the fourth and fifth attempts, the time delays are the same.
Time delay settings for the
DEL_INIT_2
signal
•
Str 2 delay shot 1
•
Str 2 delay shot 2
•
Str 2 delay shot 3
•
Str 2 delay shot 4
Time delay settings for the
DEL_INIT_3
signal
•
Str 3 delay shot 1
•
Str 3 delay shot 2
•
Str 3 delay shot 3
Control functions
1MRS758755 C
660
REC615 & RER615
Technical Manual
Содержание Relion REC615
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......