3.1.16
DNP3 settings
Table 23: DNP3 settings
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
5=off
Operation Off / On
Port
1=COM 1
2=COM 2
3=Ethernet - TCP 1
4=Ethernet TCP +UDP 1
3=Ethernet - TCP 1
Communication interface
selection
Unit address
1...65519
1
1
DNP unit address
Master address
1...65519
1
3
DNP master and UR ad-
dress
Mapping select
1...2
1
1
Mapping select
ClientIP
0.0.0.0
IP address of client
TCP port
20000...65535
1
20000
TCP Port used on ether-
net communication
TCP write authority
0=No clients
1=Reg. clients
2=All clients
2=All clients
0=no client controls
allowed; 1=Controls al-
lowed by registered cli-
ents; 2=Controls allowed
by all clients
Link keep-alive
0...65535
s
1
0
Link keep-alive interval
for DNP
Validate master addr 1=Disable
2=Enable
1=Disable
Validate master address
on receive
Self address
1=Disable
2=Enable
2=Enable
Support self address
query function
Need time interval
0...65535
min
1
30
Period to set IIN need
time bit
Time format
0=UTC
1=Local
1=Local
UTC or local. Coordinate
with master.
CROB select timeout 1...65535
s
1
10
Control Relay Output
Block select timeout
Data link confirm
0=Never
1=Only Multiframe
2=Always
0=Never
Data link confirm mode
Data link confirm TO 100...65535
ms
1
3000
Data link confirm time-
out
Data link retries
0...65535
1
3
Data link retries count
Data link Rx to Tx de-
lay
0...255
ms
1
0
Turnaround transmission
delay
Data link inter char
delay
0...20
char
1
4
Inter character delay for
incoming messages
Data link frame
length
50...292
bytes
1
292
Data link maximum
frame length
Table continues on the next page
Basic functions
1MRS758755 C
54
REC615 & RER615
Technical Manual