![ABB Relion REC615 Скачать руководство пользователя страница 322](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253322.webp)
Parameter
Values (Range)
Unit
Step
Default
Description
3=Inverse reset
Operation mode
1=Phase angle
2=IoSin
3=IoCos
4=Phase angle 80
5=Phase angle 88
1=Phase angle
Operation criteria
Enable voltage limit 0=False
1=True
1=True
Enable voltage limit
Table 354: DEFLPDEF Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Curve parameter A 0.0086...120.0000
1
28.2000
Parameter A for
customer program-
mable curve
Curve parameter B 0.0000...0.7120
1
0.1217
Parameter B for
customer program-
mable curve
Curve parameter C 0.02...2.00
1
2.00
Parameter C for
customer program-
mable curve
Curve parameter D 0.46...30.00
1
29.10
Parameter D for
customer program-
mable curve
Curve parameter E 0.0...1.0
1
1.0
Parameter E for
customer program-
mable curve
Table 355: DEFLPDEF Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
Minimum operate
time
50...60000
ms
1
50
Minimum operate
time for IDMT
curves
Allow Non Dir
0=False
1=True
0=False
Allows prot activa-
tion as non-dir
when dir info is in-
valid
Measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT
Selects used meas-
urement mode
Min operate current 0.005...1.000
xIn
0.001
0.005
Minimum operating
current
Min operate volt-
age
0.01...1.00
xUn
0.01
0.01
Minimum operating
voltage
Correction angle
0.0...10.0
deg
0.1
0.0
Angle correction
Pol reversal
0=False
1=True
0=False
Rotate polarizing
quantity
Io signal Sel
1=Measured Io
2=Calculated Io
1=Measured Io
Selection for used
Io signal
Table continues on the next page
Protection functions
1MRS758755 C
322
REC615 & RER615
Technical Manual