![ABB Relion REC615 Скачать руководство пользователя страница 677](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253677.webp)
In case there are multiple CBBs allowed for execution, the CBB with the smallest
number is chosen. For example, if CBB2 and CBB4 request an execution, CBB2 is
allowed to execute the shot.
The auto-reclose function can perform up to five auto-reclose shots or cycles.
9.4.6.3
Configuration examples
OR
CB_ TRIP
Circuit breaker position
information from binary input
Conditions to verify if circuit breaker
is ready to be reclosed
CB_ CLOSE
FPHLPTOC
I_A
I_B
START
OPERATE
I_C
BLOCK
ENA_ MULT
PHHPTOC
I_A
I_B
START
OPERATE
I_C
BLOCK
ENA_ MULT
FEFLPTOC
Io
BLOCK
START
OPERATE
ENA_ MULT
DARREC
OPEN_CB
CLOSE_CB
CMD_ WAIT
INPRO
LOCKED
PROT_ CRD
UNSUC_ RECL
DEL_ INIT_4
DEL_ INIT_3
DEL_ INIT_2
INIT_6
INIT_5
INIT_4
INIT_3
INIT_2
INIT_1
SYNC
INC_ SHOTP
CB_ READY
CB_ POS
RECL_ON
INHIBIT_ RECL
BLK_ RCLM_T
BLK_ RECL_T
BLK_ THERM
AR_ON
READY
Figure 341: Example connection between protection and autoreclosing functions in
protection relay configuration
It is possible to create several sequences for a configuration.
Autoreclose sequences for overcurrent and non-directional earth-fault protection
applications where high speed and delayed autoreclosings are needed can be as
follows:
Example 1.
The sequence is implemented by two shots which have the same reclosing
time for all protection functions, namely I>>, I> and Io>. The initiation of
the shots is done by activating the operating signals of the protection
functions.
1MRS758755 C