![ABB Relion REC615 Скачать руководство пользователя страница 61](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253061.webp)
Warning indication
Warning code
Additional information
Watchdog reset
Warning
Power down det.
11
The auxiliary supply voltage has
dropped too low.
Warning
IEC61850 error
20
Error when building the IEC 61850
data model.
Warning
Modbus error
21
Error in the Modbus communication.
Warning
DNP3 error
22
Error in the DNP3 communication.
Warning
Dataset error
24
Error in the Data set(s).
Warning
Report cont. error
25
Error in the Report control block(s).
Warning
GOOSE contr. error
26
Error in the GOOSE control block(s).
Warning
SCL config error
27
Error in the SCL configuration file or
the file is missing.
Warning
Logic error
28
Too many connections in the config-
uration.
Warning
SMT logic error
29
Error in the SMT connections.
Warning
GOOSE input error
30
Error in the GOOSE connections.
ACT error
31
Error in the ACT connections.
Warning
GOOSE Rx. error
32
Error in the GOOSE message receiv-
ing.
Warning
AFL error
33
Analog channel configuration error.
Warning
SMV config error
34
Error in the SMV configuration.
Warning
Comm. channel down
35
Redundant Ethernet (HSR/PRP)
communication interrupted.
Warning
40
A new composition has not been ac-
knowledged/accepted.