Parameter
Values (Range)
Unit
Step
Default
Description
-27=Recloser J
-28=Recloser Kg
-29=Recloser Kp
-30=Recloser L
-31=Recloser M
-32=Recloser N
-33=Recloser P
-34=Recloser R
-35=Recloser T
-36=Recloser V
-37=Recloser W
-38=Recloser Y
-39=Recloser Z
Voltage Mem time
0...3000
ms
1
40
Voltage memory time
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward
Directional mode
Characteristic an-
gle
-179...180
deg
1
60
Characteristic angle
Pol quantity
1=Self pol
4=Neg. seq. volt.
5=Cross pol
7=Pos. seq. volt.
5=Cross pol
Reference quantity used to
determine fault direction
Table 270: FDPHLPDOC Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value Mult
0.8...10.0
0.1
1.0
Multiplier for scaling the start
value
Time multiplier
0.05...15.00
0.01
1.00
Time multiplier in IEC/ANSI
IDMT curves
Type of reset curve 1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate
Selection of reset curve type
Max forward angle 0...90
deg
1
80
Maximum phase angle in for-
ward direction
Max reverse angle
0...90
deg
1
80
Maximum phase angle in re-
verse direction
Min forward angle
0...90
deg
1
80
Minimum phase angle in for-
ward direction
Min reverse angle
0...90
deg
1
80
Minimum phase angle in re-
verse direction
Table 271: FDPHLPDOC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
1=on
Operation Off / On
Table continues on the next page
Protection functions
1MRS758755 C
256
REC615 & RER615
Technical Manual