![ABB Relion REC615 Скачать руководство пользователя страница 427](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253427.webp)
PHPTOV Monitored data
Table 437: PHPTOV Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start
time / operate
time
PHPTOV
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.4.1.10
Technical data
Table 438: PHPTOV Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured voltage: f
n
±2 Hz
±1.5% of the set value or ±0.002 × U
n
Start time
1
2
U
Fault
= 1.1 × set
Start
value
Minimum
Typical
Maximum
23 ms
27 ms
31 ms
Reset time
Typically 40 ms
Reset ratio
Depends on the set
Relative hysteresis
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
4.4.1.11
Technical revision history
Table 439: PHPTOV Technical revision history
Technical revision
Change
B
Step value changed from 0.05 to 0.01 for the
Time multiplier
setting.
C
Curve Sat relative max range widened from
3.0 to 10.0 % and default value changed from
2.0 to 0.0 %.
D
Added setting
Type of time reset
.
1
Start value = 1.0 × U
n
, Voltage before fault = 0.9 × U
n
, f
n
= 50 Hz, overvoltage in one phase-to-
phase with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2
Includes the delay of the signal output contact
3
Maximum
Start value = 1.20 × U
n
,
Start value multiples in range of 1.10...2.00
1MRS758755 C
Protection functions
REC615 & RER615
Technical Manual
427
Содержание Relion REC615
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......