Table 257: Measurement modes supported by (F)DPHxPDOC stages
Measurement mode
(F)DPHLPDOC
DPHHPDOC
RMS
x
x
DFT
x
x
Peak-to-Peak
x
x
4.1.2.6
Directional overcurrent characteristics
The forward and reverse sectors are defined separately. The forward operation area
is limited with the
Min forward angle and Max forward angle settings. The reverse
operation area is limited with the
Min reverse angle and Max reverse angle settings.
The sector limits are always given as positive degree values.
In the forward operation area, the
Max forward angle setting gives the
counterclockwise sector and the
Min forward angle setting gives the corresponding
clockwise sector, measured from the
Characteristic angle setting.
In the backward operation area, the
Max reverse angle setting gives the
counterclockwise sector and the
Min reverse angle setting gives the corresponding
clockwise sector, a measurement from the
Characteristic angle setting that has
been rotated 180 degrees.
Relay characteristic angle (RCA) is set positive if the operating current lags the
polarizing quantity and negative if the operating current leads the polarizing
quantity.
Protection functions
1MRS758755 C
242
REC615 & RER615
Technical Manual