![ABB Relion REC615 Скачать руководство пользователя страница 591](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253591.webp)
Parameter
Values (Range)
Unit
Step
Default
Description
V high limit res
0.00...4.00
xUn
1
0.05
High warning volt-
age limit
V deadband res
100...100000
1
10000
Deadband configu-
ration value for in-
tegral calculation.
(percentage of dif-
ference between
min and max as
0,001 % s)
Table 610: RESVMMXU Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Measurement
mode
1=RMS
2=DFT
2=DFT
Selects used meas-
urement mode
8.1.7.5
Monitored data
RESVMMXU Monitored data
Table 611: RESVMMXU Monitored data
Name
Type
Values (Range)
Unit
Description
Uo-kV
FLOAT32
0.00...4.00
xUn
Measured residu-
al voltage
BLOCK
BOOLEAN
0=False
1=True
Block signal for
all binary out-
puts
HIGH_ALARM
BOOLEAN
0=False
1=True
High alarm
HIGH_WARN
BOOLEAN
0=False
1=True
High warning
U_INST_RES
FLOAT32
0.00...4.00
xUn
Residual voltage
Amplitude, mag-
nitude of instan-
taneous value
U_ANGL_RES
FLOAT32
-180.00...180.00
deg
Residual voltage
angle
U_DB_RES
FLOAT32
0.00...4.00
xUn
Residual voltage
Amplitude, mag-
nitude of repor-
ted value
U_DMD_RES
FLOAT32
0.00...4.00
xUn
Demand value of
residual voltage
U_RANGE_RES
Enum
0=normal
1=high
2=low
Residual voltage
Amplitude range
1MRS758755 C
Measurement functions
REC615 & RER615
Technical Manual
591
Содержание Relion REC615
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...