3.17.1.4
NOT function block
Function block
Figure 67: Function block
Functionality
NOT is used to generate combinatory expressions with Boolean variables.
NOT inverts the input signal.
Signal
Table 114: NOT Input signal
Name
Type
Default
Description
I
BOOLEAN
0
Input signal
Table 115: NOT Output signal
Name
Type
Description
O
BOOLEAN
Output signal
Settings
The function does not have any parameters available in LHMI or PCM600.
3.17.1.5
MAX3 function block
Function block
Figure 68: Function block
Functionality
The maximum function MAX3 selects the maximum value from three analog values.
Disconnected inputs and inputs whose quality is bad are ignored. If all inputs are
disconnected or the quality is bad, MAX3 output value is set to -2^21.
1MRS758755 C
Basic functions
REC615 & RER615
Technical Manual
137