![ABB Relion REC615 Скачать руководство пользователя страница 628](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253628.webp)
value. The functions are designed according to the IEC 61850-7-4 standard with
logical nodes CILO, CSWI and XSWI/XCBR.
The circuit breaker and disconnector control functions have an operation counter
for closing and opening cycles. The counter value can be read and written remotely
from the place of operation or via LHMI.
9.1.4
Operation principle
Status indication and validity check
The object state is defined by two digital inputs,
POSOPEN
and
POSCLOSE
, which
are also available as outputs
OPENPOS
and
CLOSEPOS
together with the
OKPOS
according to
. The debouncing and short disturbances in an input are
eliminated by filtering. The binary input filtering time can be adjusted separately
for each digital input used by the function block. The validity of the digital inputs
that indicate the object state is used as additional information in indications and
event logging. The reporting of faulty or intermediate position of the apparatus
occurs after the
Event delay setting, assuming that the circuit breaker is still in a
corresponding state.
Table 647: Status indication
Input
Status
Output
POSOPEN
POSCLOSE
POSITION
(Monitored
data)
OKPOS
OPENPOS
CLOSEPOS
1=True
0=False
1=Open
1=True
1=True
0=False
0=False
1=True
2=Closed
1=True
0=False
1=True
1=True
1=True
3=Faulty/Bad
(11)
0=False
0=False
0=False
0=False
0=False
0=Intermedi-
ate (00)
0=False
0=False
0=False
Enabling and blocking
CBXCBR and DCXSWI have an enabling and blocking functionality for interlocking
and synchrocheck purposes.
Circuit breaker control CBXCBR
Normally, the CB closing is enabled (that is,
CLOSE_ENAD
signal is TRUE)
by activating both
ENA_CLOSE
and
SYNC_OK
inputs. Typically, the
ENA_CLOSE
comes from the interlocking, and
SYNC_OK
comes from the synchronism and
energizing check. The input
SYNC_ITL_BYP
can be used for bypassing this control.
The
SYNC_ITL_BYP
input can be used to activate
CLOSE_ENAD
discarding the
ENA_CLOSE
and
SYNC_OK
input states. However, the
BLK_CLOSE
input always blocks
the
CLOSE_ENAD
output.
The CB opening (
OPEN_ENAD
) logic is the same as CB closing logic, except
that
SYNC_OK
is used only in closing. The
SYNC_ITL_BYP
input is used in both
CLOSE_ENAD
and
OPEN_ENAD
logics.
Control functions
1MRS758755 C
628
REC615 & RER615
Technical Manual