Parameter
Values (Range)
Unit
Step
Default
Description
Curve parameter C 0.02...2.00
1
2.00
Parameter C for
customer program-
mable curve
Curve parameter D 0.46...30.00
1
29.10
Parameter D for
customer program-
mable curve
Curve parameter E 0.0...1.0
1
1.0
Parameter E for
customer program-
mable curve
Table 393: HAEFPTOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
10
20
Reset delay time
4.2.5.8
Monitored data
HAEFPTOC Monitored data
Table 394: HAEFPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start
time / operate
time
I_HARM_RES
FLOAT32
0.0...30000.0
A
Calculated har-
monics current
BLKD_I_REF
BOOLEAN
0=False
1=True
Current compari-
son status indi-
cator
HAEFPTOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.2.5.9
Technical data
Table 395: HAEFPTOC Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: f
n
±2 Hz
±5% of the set value or ±0.004 × I
n
Start time
1
2
Typically 77 ms
Reset time
Typically 40 ms
Table continues on the next page
1
Fundamental frequency current = 1.0 × I
n
, harmonics current before fault = 0.0 × I
n
, harmonics
fault current 2.0 ×
Start value, results based on statistical distribution of 1000 measurements
2
Includes the delay of the signal output contact
1MRS758755 C
Protection functions
REC615 & RER615
Technical Manual
375