8.1.9.2
Function block
Figure 299: Function block
8.1.9.3
Signals
CSMSQI Input signals
Table 620: CSMSQI Input signals
Name
Type
Default
Description
I
0
SIGNAL
0
Zero sequence cur-
rent
I
1
SIGNAL
0
Positive sequence
current
I
2
SIGNAL
0
Negative sequence
current
8.1.9.4
Settings
CSMSQI Non group settings
Table 621: CSMSQI Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Ps Seq A Hi high
Lim
0.00...40.00
xIn
1
1.40
High alarm current
limit for positive
sequence current
Ps Seq A high limit
0.00...40.00
xIn
1
1.20
High warning cur-
rent limit for pos-
itive sequence cur-
rent
Ps Seq A low limit
0.00...40.00
xIn
1
0.00
Low warning cur-
rent limit for pos-
itive sequence cur-
rent
Ps Seq A low low
Lim
0.00...40.00
xIn
1
0.00
Low alarm current
limit for positive
sequence current
Ps Seq A deadband 100...100000
1
2500
Deadband configu-
ration value for
positive sequence
current for inte-
gral calculation.
Table continues on the next page
1MRS758755 C
Measurement functions
REC615 & RER615
Technical Manual
595