![ABB Relion REC615 Скачать руководство пользователя страница 366](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253366.webp)
Parameter
Values (Range)
Unit
Step
Default
Description
Conductance re-
verse
-500.00...500.00
mS
0.01
-1.00
Conductance
threshold in reverse
direction
Susceptance for-
ward
-500.00...500.00
mS
0.01
1.00
Susceptance
threshold in for-
ward direction
Susceptance re-
verse
-500.00...500.00
mS
0.01
-1.00
Susceptance
threshold in reverse
direction
Table 382: EFPADM Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Conductance tilt
Ang
-30...30
deg
1
0
Tilt angle of con-
ductance boundary
line
Susceptance tilt
Ang
-30...30
deg
1
0
Tilt angle of sus-
ceptance boundary
line
Table 383: EFPADM Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 384: EFPADM Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Admittance Clc
mode
1=Normal
2=Delta
1=Normal
Admittance calcula-
tion mode
Reset delay time
0...60000
ms
1
20
Reset delay time
Pol reversal
0=False
1=True
0=False
Rotate polarizing
quantity
Min operate current 0.01...1.00
xIn
0.01
0.01
Minimum operating
current
Min operate volt-
age
0.01...1.00
xUn
0.01
0.01
Minimum operating
voltage
Io signal Sel
1=Measured Io
2=Calculated Io
1=Measured Io
Selection for used
Io signal
Uo signal Sel
1=Measured Uo
2=Calculated Uo
1=Measured Uo
Selection for used
Uo signal