Parameter
Values (Range)
Unit
Step
Default
Description
Dead line value
0.1...0.8
xUn
0.1
0.2
Voltage low limit
line for energizing
check
Live line value
0.2...1.0
xUn
0.1
0.8
Voltage high limit
line for energizing
check
Dead bus value
0.1...0.8
xUn
0.1
0.2
Voltage low limit
bus for energizing
check
Live bus value
0.2...1.0
xUn
0.1
0.5
Voltage high limit
bus for energizing
check
Max energizing V
0.50...1.15
xUn
0.01
1.05
Maximum voltage
for energizing
Table 678: SECRSYN Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Control mode
1=Continuous
2=Command
1=Continuous
Selection of syn-
chro check com-
mand or Continu-
ous control mode
Close pulse
200...60000
ms
10
200
Breaker closing
pulse duration
Phase shift
-180...180
deg
1
0
Correction of phase
difference between
measured U_BUS
and U_LINE
Minimum Syn time
0...60000
ms
10
0
Minimum time to
accept synchroniz-
ing
Maximum Syn time 100...6000000
ms
10
2000
Maximum time to
accept synchroniz-
ing
Energizing time
100...60000
ms
10
100
Time delay for en-
ergizing check
Closing time of CB
40...250
ms
10
60
Closing time of the
breaker
Voltage source
switch
0=False
1=True
0=False
Voltage source
switch
9.3.8
Monitored data
9.3.8.1
SECRSYN Monitored data
Table 679: SECRSYN Monitored data
Name
Type
Values (Range)
Unit
Description
ENERG_STATE
Enum
0=Unknown
1=Both Live
2=Live L, Dead B
3=Dead L, Live B
Energization
state of Line and
Bus
Table continues on the next page
Control functions
1MRS758755 C
654
REC615 & RER615
Technical Manual