Name
Type
Description
ST_B
BOOLEAN
Start phase B
ST_C
BOOLEAN
Start phase C
4.1.4.7
Settings
Table 298: PHPTUC Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Current block value
0.00...0.50
xIn
0.01
0.10
Low current setting to block in-
ternally
Start value
0.01...1.00
xIn
0.01
0.50
Current setting to start
Operate delay time
50...200000
ms
10
2000
Operate delay time
Table 299: PHPTUC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Operation mode
1=Three Phase
2=Single Phase
1=Three Phase
Number of phases needed to
start
Table 300: PHPTUC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
4.1.4.8
Monitored data
Table 301: PHPTUC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start
time / operate
time
PHPTUC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Protection functions
1MRS758755 C
276
REC615 & RER615
Technical Manual