![ABB Relion REC615 Скачать руководство пользователя страница 290](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253290.webp)
Table 324: EFHPTOC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Curve parameter A 0.0086...120.0000
1
28.2000
Parameter A for
customer program-
mable curve
Curve parameter B 0.0000...0.7120
1
0.1217
Parameter B for
customer program-
mable curve
Curve parameter C 0.02...2.00
1
2.00
Parameter C for
customer program-
mable curve
Curve parameter D 0.46...30.00
1
29.10
Parameter D for
customer program-
mable curve
Curve parameter E 0.0...1.0
1
1.0
Parameter E for
customer program-
mable curve
Table 325: EFHPTOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Minimum operate
time
20...60000
ms
1
20
Minimum operate
time for IDMT
curves
Reset delay time
0...60000
ms
1
20
Reset delay time
Measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT
Selects used meas-
urement mode
Io signal Sel
1=Measured Io
2=Calculated Io
1=Measured Io
Selection for used
Io signal
Table 326: EFIPTOC Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
1.00...40.00
xIn
0.01
1.00
Start value
Start value Mult
0.8...10.0
0.1
1.0
Multiplier for scal-
ing the start value
Operate delay time 20...200000
ms
10
20
Operate delay time
Table 327: EFIPTOC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Protection functions
1MRS758755 C
290
REC615 & RER615
Technical Manual
Содержание Relion REC615
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...