5.3.5
Application
All trip signals from different protection functions are routed through the trip logic.
The most simplified application of the logic function is linking the trip signal and
ensuring that the signal is long enough.
The tripping logic in the protection relay is intended to be used in the three-phase
tripping for all fault types (3ph operating). To prevent the closing of a circuit breaker
after a trip, TRPPTRC can block the CBXCBR closing.
TRPPTRC is intended to be connected to one trip coil of the corresponding circuit
breaker. If tripping is needed for another trip coil or another circuit breaker which
needs, for example, different trip pulse time, another trip logic function can be
used. The two instances of the PTRC function are identical, only the names of the
functions, TRPPTRC1 and TRPPTRC2, are different. Therefore, even if all references
are made only to TRPPTRC1, they also apply to TRPPTRC2.
The inputs from the protection functions are connected to the
OPERATE
input.
Usually, a logic block OR is required to combine the different function outputs to
this input. The
TRIP
output is connected to the binary outputs on the IO board. This
signal can also be used for other purposes within the protection relay, for example
when starting the breaker failure protection.
TRPPTRC is used for simple three-phase tripping applications.
OR
TRIP
CL_LKOUT
BLOCK
RST_LKOUT
TRPPTRC1
OPERATE
NSPTOC2_OPERATE
DPHLPDOC1_OPERATE
DPHLPDOC2_OPERATE
DPHHPDOC1_OPERATE
DEFLPDEF1_OPERATE
DEFHPDEF1_OPERATE
EFPADM1_OPERATE
EFPADM2_OPERATE
EFPADM3_OPERATE
WPWDE1_OPERATE
WPWDE2_OPERATE
DEFLPDEF2_OPERATE
X100 PO1
PDNSPTOC1_OPERATE
WPWDE3_OPERATE
NSPTOC1_OPERATE
ROVPTOV1_OPERATE
ROVPTOV2_OPERATE
PHPTOV1_OPERATE
PHPTOV2_OPERATE
PHPTOV3_OPERATE
PHPTUV1_OPERATE
PHPTUV2_OPERATE
PHPTUV3_OPERATE
NSPTOV1_OPERATE
PSPTUV1_OPERATE
PHLPTOC1_OPERATE
EFLPTOC1_OPERATE
LSHDPFR1_OPERATE
AND
PHHPTOC1_OPERATE
EFHPTOC1_OPERATE
SPCGGIO1_CNT_LOGIC_ENA
AND
PHIPTOC1_START
EFIPTOC1_START
SPCGGIO1_SW_MODE_ENA
FRPFRQ2_OPERATE
FRPFRQ1_OPERATE
Figure 245: Typical TRPPTRC connection with REC615
1MRS758755 C
Protection related functions
REC615 & RER615
Technical Manual
493