![ABB Relion REC615 Скачать руководство пользователя страница 521](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253521.webp)
Name
Type
Values (Range)
Unit
Description
Flt to Lod Cur ra-
tio
FLOAT32
0.00...60000.00
Fault to load cur-
rent ratio
Equivalent load
Dis
FLOAT32
0.00...1.00
Estimated equiv-
alent load dis-
tance
XC0F Calc
FLOAT32
0.0...1000000.0
ohm
Estimated PhE
capacitive reac-
tance of the line
Pre fault time
Timestamp
Pre-fault time
A Pre Flt Phs A
Magn
FLOAT32
0.00...40.00
xIn
Pre-fault current
phase A, magni-
tude
A Pre Flt Phs A
Angl
FLOAT32
-180.00...180.00
deg
Pre-fault current
phase A, angle
A Pre Flt Phs B
Magn
FLOAT32
0.00...40.00
xIn
Pre-fault current
phase B, magni-
tude
A Pre Flt Phs B
Angl
FLOAT32
-180.00...180.00
deg
Pre-fault current
phase B, angle
A Pre Flt Phs C
Magn
FLOAT32
0.00...40.00
xIn
Pre-fault current
phase C, magni-
tude
A Pre Flt Phs C
Angl
FLOAT32
-180.00...180.00
deg
Pre-fault current
phase C, angle
V Pre Flt Phs A
Magn
FLOAT32
0.00...40.00
xIn
Pre-fault voltage
phase A, magni-
tude
V Pre Flt Phs A
Angl
FLOAT32
-180.00...180.00
deg
Pre-fault voltage
phase A, angle
V Pre Flt Phs B
Magn
FLOAT32
0.00...40.00
xIn
Pre-fault voltage
phase B, magni-
tude
V Pre Flt Phs B
Angl
FLOAT32
-180.00...180.00
deg
Pre-fault voltage
phase B, angle
V Pre Flt Phs C
Magn
FLOAT32
0.00...40.00
xIn
Pre-fault voltage
phase C, magni-
tude
V Pre Flt Phs C
Angl
FLOAT32
-180.00...180.00
deg
Pre-fault voltage
phase C, angle
A Flt Phs A Magn FLOAT32
0.00...40.00
xIn
Fault current
phase A, magni-
tude
A Flt Phs A angle FLOAT32
-180.00...180.00
deg
Fault current
phase A, angle
Table continues on the next page