![ABB Relion REC615 Скачать руководство пользователя страница 599](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253599.webp)
8.1.10.2
Function block
Figure 300: Function block
8.1.10.3
Signals
VSMSQI Input signals
Table 625: VSMSQI Input signals
Name
Type
Default
Description
U
0
SIGNAL
0
Zero sequence volt-
age
U
1
SIGNAL
0
Positive phase se-
quence voltage
U
2
SIGNAL
0
Negative phase se-
quence voltage
8.1.10.4
Settings
VSMSQI Non group settings
Table 626: VSMSQI Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Ps Seq V Hi high
Lim
0.00...4.00
xUn
1
1.40
High alarm voltage
limit for positive
sequence voltage
Ps Seq V high limit
0.00...4.00
xUn
1
1.20
High warning volt-
age limit for posi-
tive sequence volt-
age
Ps Seq V low limit
0.00...4.00
xUn
1
0.00
Low warning volt-
age limit for posi-
tive sequence volt-
age
Ps Seq V low low
Lim
0.00...4.00
xUn
1
0.00
Low alarm voltage
limit for positive
sequence voltage
Ps Seq V deadband 100...100000
1
10000
Deadband configu-
ration value for
positive sequence
voltage for inte-
gral calculation.
(percentage of dif-
ference between
min and max as
0,001 % s)
Ng Seq V Hi high
Lim
0.00...4.00
xUn
1
0.20
High alarm voltage
limit for negative
sequence voltage
Table continues on the next page
1MRS758755 C
Measurement functions
REC615 & RER615
Technical Manual
599