Parameter
Values (Range)
Unit
Step
Default
Description
5=off
Min operate current 0.01...1.00
xIn
0.01
0.10
Minimum operating
current
Min operate volt-
age
0.01...1.00
xUn
0.01
0.30
Minimum operating
voltage
Table 500: DPSRDIR Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
4.6.1.8
Monitored data
Table 501: DPSRDIR Monitored data
Name
Type
Values (Range)
Unit
Description
ANGLE_RCA
FLOAT32
-180.00...180.00
deg
Angle between operat-
ing angle and charac-
teristic angle
DPSRDIR
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.7
Multipurpose protection MAPGAPC
4.7.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Multipurpose protection
MAPGAPC
MAP
MAP
4.7.2
Function block
Figure 231: Function block
1MRS758755 C
Protection functions
REC615 & RER615
Technical Manual
471