![ABB Relion REC615 Скачать руководство пользователя страница 455](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253455.webp)
Parameter
Values (Range)
Unit
Step
Default
Description
Operate Tm Freq
80...200000
ms
10
200
Operate delay time
for frequency
Operate Tm df/dt
120...200000
ms
10
400
Operate delay time
for frequency rate
of change
Table 481: FRPFRQ Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 482: FRPFRQ Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay Tm
Freq
0...60000
ms
1
0
Reset delay time
for frequency
Reset delay Tm
df/dt
0...60000
ms
1
0
Reset delay time
for rate of change
4.5.1.8
Monitored data
Table 483: FRPFRQ Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Start duration
ST_DUR_OFRQ
FLOAT32
0.00...100.00
%
Start duration
ST_DUR_UFRQ
FLOAT32
0.00...100.00
%
Start duration
ST_DUR_FRG
FLOAT32
0.00...100.00
%
Start duration
FRPFRQ
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.5.1.9
Technical data
Table 484: FRPFRQ Technical data
Characteristic
Value
Operation accuracy
f>/f<
±5 mHz
df/dt
±50 mHz/s (in range |df/dt| <5 Hz/s)
±2.0% of the set value (in range 5 Hz/s < |df/dt| < 15 Hz/s)
Start time
f>/f<
<80 ms
df/dt
<120 ms
Table continues on the next page
1MRS758755 C
Protection functions
REC615 & RER615
Technical Manual
455
Содержание Relion REC615
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......