Parameter
Values (Range)
Unit
Step
Default
Description
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward
Directional mode
Characteristic an-
gle
-179...180
deg
1
60
Characteristic angle
Max forward angle 0...90
deg
1
80
Maximum phase angle in for-
ward direction
Max reverse angle
0...90
deg
1
80
Maximum phase angle in re-
verse direction
Min forward angle
0...90
deg
1
80
Minimum phase angle in for-
ward direction
Min reverse angle
0...90
deg
1
80
Minimum phase angle in re-
verse direction
Table 274: DPHLPDOC Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Type of reset curve 1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate
Selection of reset curve type
Voltage Mem time
0...3000
ms
1
40
Voltage memory time
Pol quantity
1=Self pol
4=Neg. seq. volt.
5=Cross pol .
7=Pos. seq. volt.
5=Cross pol
Reference quantity used to
determine fault direction
Table 275: DPHLPDOC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Num of start pha-
ses
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3
Number of phases
required for oper-
ate activation
Curve parameter A 0.0086...120.0000
1
28.2000
Parameter A for
customer program-
mable curve
Table continues on the next page
Protection functions
1MRS758755 C
258
REC615 & RER615
Technical Manual