4.1.2.9
Settings
Table 269: FDPHLPDOC Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.05...5.00
xIn
0.01
0.05
Start value
Operate delay time 40...200000
ms
10
40
Operate delay time
Operating curve
type
1=ANSI Ext. inv.
2=ANSI Very inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
-1=Recloser 1
-2=Recloser 2
-3=Recloser 3
-4=Recloser 4
-5=Recloser 5
-6=Recloser 6
-7=Recloser 7
-8=Recloser 8
-9=Recloser 8+
-10=Recloser 8*
-11=Recloser 9
-12=Recloser 11
-13=Recloser 13
-14=Recloser 14
-15=Recloser 15
-16=Recloser 16
-17=Recloser 17
-18=Recloser 18
-19=Recloser A
-20=Recloser B
-21=Recloser C
-22=Recloser D
-23=Recloser E
-24=Recloser F
-25=Recloser G
-26=Recloser H
15=IEC Def. Time
Selection of time delay curve
type
Table continues on the next page
1MRS758755 C
Protection functions
REC615 & RER615
Technical Manual
255