![ABB Relion REC615 Скачать руководство пользователя страница 856](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253856.webp)
14.11
Ethernet interfaces
Table 761: Ethernet interfaces
Ethernet
interface
Protocol
Cable
Data transfer rate
Front
TCP/IP
protocol
Standard Ethernet CAT 5 cable
with RJ-45 connector
10 MBits/s
Rear
TCP/IP
protocol
Shielded twisted pair CAT 5e cable
with
RJ-45 connector or fibre-optic ca-
ble with LC connector
100 MBits/s
14.12
Serial rear interface
Table 762: Serial rear interface
Type
Counter connector
Serial port (X5)
10-pin counter connector Weidmüller BL
3.5/10/180F AU OR BEDR
or
9-pin counter connector Weidmüller BL
3.5/9/180F AU OR BEDR
1
Serial port (X16)
9-pin D-sub connector DE-9
Serial port (X12)
Optical ST-connector
14.13
Fibre-optic communication link
Table 763: Fibre-optic communication link
Connector
Fibre type
Wave length
Max. distance
Permitted path
attenuation
1
LC
MM 62.5/125 or
1300 nm
2 km
<8 dB
Table continues on the next page
1
Depending on the optional communication module
1
Maximum allowed attenuation caused by connectors and cable together