the corresponding analog channel. In addition, the user can enable or disable each
analog channel of the disturbance recorder by setting the
Operation parameter of
the corresponding analog channel to "on" or "off".
All analog channels of the disturbance recorder that are enabled and have a valid
signal type mapped are included in the recording.
8.2.2.2
Triggering alternatives
The recording can be triggered by any or several of the following alternatives:
• Triggering according to the state change of any or several of the binary channels
of the disturbance recorder. The user can set the level sensitivity with the
Level
trigger mode parameter of the corresponding binary channel.
• Triggering on limit violations of the analog channels of the disturbance recorder
(high and low limit)
• Manual triggering via the
Trig recording parameter (LHMI or communication)
• Periodic triggering.
Regardless of the triggering type, each recording generates the Recording started
and Recording made events. The Recording made event indicates that the recording
has been stored to the non-volatile memory. In addition, every analog channel
and binary channel of the disturbance recorder has its own
Channel triggered
parameter. Manual trigger has the
Manual triggering parameter and periodic trigger
has the
Periodic triggering parameter.
Triggering by binary channels
Input signals for the binary channels of the disturbance recorder can be formed
from any of the digital signals that can be dynamically mapped. A change in the
status of a monitored signal triggers the recorder according to the configuration
and settings. Triggering on the rising edge of a digital input signal means that
the recording sequence starts when the input signal is activated. Correspondingly,
triggering on the falling edge means that the recording sequence starts when the
active input signal resets. It is also possible to trigger from both edges. In addition,
if preferred, the monitored signal can be non-triggering. The trigger setting can be
set individually for each binary channel of the disturbance recorder with the
Level
trigger mode parameter of the corresponding binary channel.
Triggering by analog channels
The trigger level can be set for triggering in a limit violation situation. The user can
set the limit values with the
High trigger level and Low trigger level parameters of
the corresponding analog channel. Both high level and low level violation triggering
can be active simultaneously for the same analog channel. If the duration of
the limit violation condition exceeds the filter time of approximately 50 ms, the
recorder triggers. In case of a low level limit violation, if the measured value falls
below approximately 0.05 during the filter time, the situation is considered to be
a circuit-breaker operation and therefore, the recorder does not trigger. This is
useful especially in undervoltage situations. The filter time of approximately 50
ms is common to all the analog channel triggers of the disturbance recorder. The
value used for triggering is the calculated peak-to-peak value. Either high or low
analog channel trigger can be disabled by setting the corresponding trigger level
parameter to zero.