CTRL.LLN0.LocSta and CONTROL function block input
CTRL_STA
are applicable for
this station authority level.
“Station” and “Local + Station” control access can be reserved by using R/L
button or CONTROL function block in combination with IEC 61850 data object
CTRL.LLN0.LocSta.
Table 189: Station authority level “L,S,S+R,L+S,L+S+R” using R/L button
L/R Control
L/R Control status
Control access
R/L button
CTRL.LLN0.LocS
ta
1
CTRL.LLN0.MltL
ev
L/R state
CTRL.LLN0.Loc
KeyHMI
Local user
IEC 61850 client
2
IEC 61850
client
3
Local
FALSE
FALSE
1
x
Remote
FALSE
TRUE
7
x
x
Remote
TRUE
FALSE
3
x
Local + Remote
FALSE
TRUE
6
x
x
x
Local + Remote
TRUE
TRUE
5
x
x
Off
FALSE
FALSE
0
Table 190: Station authority level “L,S,S+R,L+S,L+S+R” using CONTROL function block
L/R Control
L/R Control status
Control access
R/L button
CTRL.LLN0.LocS
ta
1
CTRL.LLN0.MltL
ev
L/R state
CTRL.LLN0.Loc
KeyHMI
Local user
IEC 61850 client
2
IEC 61850
client
3
CTRL_OFF
FALSE
FALSE
0
CTRL_LOC
FALSE
FALSE
1
x
CTRL_STA
FALSE
FALSE
3
x
CTRL_REM
4
TRUE
TRUE
3
x
CTRL_REM
FALSE
TRUE
7
x
x
CTRL_ALL
FALSE
TRUE
6
x
x
x
CTRL_ALL
4
TRUE
TRUE
5
x
x
3.17.11.8
Signals
Table 191: CONTROL input signals
Name
Type
Default
Description
CTRL_OFF
BOOLEAN
0
Control input OFF
CTRL_LOC
BOOLEAN
0
Control input Local
CTRL_STA
BOOLEAN
0
Control input Station
CTRL_REM
BOOLEAN
0
Control input Remote
CTRL_ALL
BOOLEAN
0
Control input All
1
Station client reserves the control operating by writing controllable point LocSta.
2
Client IEC 61850 command originator category is remote.
3
Client IEC 61850 command originator category is station.
4
CTRL_STA unconnected in application configuration. Station client reserves the control operating
by writing controllable point LocSta.
Basic functions
1MRS758755 C
170
REC615 & RER615
Technical Manual