![ABB Relion REC615 Скачать руководство пользователя страница 830](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253830.webp)
U
U
U
U
C
CA
BC
=
+
−
(
)
0
/ 3
(Equation 101)
If the
U
0
channel is not valid, it is assumed to be zero.
The phase-to-phase voltages are calculated from the phase-to-earth voltages when
VT connection is selected as "Wye" according to the equations.
U
U
U
AB
A
B
=
−
(Equation 102)
U
U
U
BC
B
C
=
−
(Equation 103)
U
U
U
CA
C
A
=
−
(Equation 104)
General function block features
1MRS758755 C
830
REC615 & RER615
Technical Manual