![ABB Relion REC615 Скачать руководство пользователя страница 93](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253093.webp)
3.11.3
Oscillation suppression
Oscillation suppression is used to reduce the load from the system when a binary
input starts oscillating. A binary input is regarded as oscillating if the number of
valid state changes (= number of events after filtering) during one second is equal
to or greater than the set oscillation level value. During oscillation, the binary input
is blocked (the status is invalid) and an event is generated. The state of the input
will not change when it is blocked, that is, its state depends on the condition before
blocking.
The binary input is regarded as non-oscillating if the number of valid state changes
during one second is less than the set oscillation level value minus the set oscillation
hysteresis value. Note that the oscillation hysteresis must be set lower than the
oscillation level to enable the input to be restored from oscillation. When the input
returns to a non-oscillating state, the binary input is deblocked (the status is valid)
and an event is generated.
Table 53: Oscillation parameters
Parameter
Value
Default
Input osc. level
2...50 events/s
30 events/s
Input osc. hyst
2...50 events/s
10 events/s
3.12
Binary outputs
The protection relay provides a number of binary outputs used for tripping,
executing local or remote control actions of a breaker or a disconnector, and for
connecting the protection relay to external annunciation equipment for indicating,
signalling and recording.
Power output contacts are used when the current rating requirements of the
contacts are high, for example, for controlling a breaker, such as energizing the
breaker trip and closing coils.
The contacts used for external signalling, recording and indicating, the signal
outputs, need to adjust to smaller currents, but they can require a minimum current
(burden) to ensure a guaranteed operation.
The protection relay provides both power output and signal output contacts. To
guarantee proper operation, the type of the contacts used are chosen based on
the operating and reset time, continuous current rating, make and carry for short
time, breaking rate and minimum connected burden. A combination of series or
parallel contacts can also be used for special applications. When appropriate, a
signal output can also be used to energize an external trip relay, which in turn can be
confiugred to energize the breaker trip or close coils.
Using an external trip relay can require an external trip circuit supervision
relay. It can also require wiring a separate trip relay contact back to the
protection relay for breaker failure protection function.
All contacts are freely programmable, except the internal fault output IRF.
1MRS758755 C
Basic functions
REC615 & RER615
Technical Manual
93
Содержание Relion REC615
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......