![ABB Relion REC615 Скачать руководство пользователя страница 636](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253636.webp)
Table 652: CBXCBR Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation mode
on/off
Select timeout
10000...300000
ms
10000
30000
Select timeout in
ms
Pulse length
10...60000
ms
1
200
Open and close
pulse length
Control model
0=status-only
1=direct-with-nor-
mal-security
4=sbo-with-en-
hanced-security
4=sbo-with-en-
hanced-security
Select control mod-
el
Operation timeout 10...60000
ms
1
500
Timeout for nega-
tive termination
Identification
CBXCBR1 switch
position
Control Object
identification
Table 653: CBXCBR Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation counter
0...10000
1
0
Breaker operation
cycles
Adaptive pulse
0=False
1=True
1=True
Stop in right posi-
tion
Event delay
0...10000
ms
1
200
Event delay of the
intermediate posi-
tion
Vendor
0
External equipment
vendor
Serial number
0
External equipment
serial number
Model
0
External equipment
model
9.1.7.2
DCXSWI Non group settings
Table 654: DCXSWI Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation mode
on/off
Select timeout
10000...300000
ms
10000
30000
Select timeout in
ms
Pulse length
10...60000
ms
1
100
Open and close
pulse length
Control model
0=status-only
1=direct-with-nor-
mal-security
4=sbo-with-en-
hanced-security
4=sbo-with-en-
hanced-security
Select control mod-
el
Operation timeout 10...60000
ms
1
30000
Timeout for nega-
tive termination
Identification
DCXSWI1 switch
position
Control Object
identification
Control functions
1MRS758755 C
636
REC615 & RER615
Technical Manual
Содержание Relion REC615
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......