Parameter
Values (Range)
Unit
Step
Default
Description
Description
SPCLGAPC1 Output
15
Generic control point description
Operation mode
0=Pulsed
1=Toggle/Persistent
-1=Off
-1=Off
Operation mode for generic con-
trol point
Pulse length
10...3600000
ms
10
1000
Pulse length for pulsed operation
mode
Description
SPCLGAPC1 Output
16
Generic control point description
3.17.15
Programmable buttons (4 buttons) FKEY4GGIO
3.17.15.1
Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Programmable but-
tons (4 buttons)
FKEY4GGIO
FKEY4GGIO
FKEY4GGIO
3.17.15.2
Function block
FKEY4GGIO
K2
K1
K3
K4
L2
L1
L3
L4
Figure 105: Function block
3.17.15.3
Functionality
The Programmable buttons function FKEY4GGIO is a simple interface between the
panel and the application. The user input from the buttons available on the front
panel is transferred to the assigned functionality and the corresponding LED is
turned ON or OFF for indication. The behavior of each function key in the specific
application is configured by connection with other application functions. This gives
maximum flexibility.
3.17.15.4
Operation principle
Inputs
L1...L4
represent the LEDs on the relay's LHMI. When an input is set to
TRUE, the corresponding LED is lit. When a function key on the LHMI is pressed, the
corresponding output
K1...K4
is set to TRUE.
Each function key has settable text descriptions for the on and off states. The
visibility of function key text descriptions on the LHMI can be selected with setting
parameter
Function key text visibility.