![ABB Relion REC615 Скачать руководство пользователя страница 434](http://html.mh-extra.com/html/abb/relion-rec615/relion-rec615_technical-manual_3045253434.webp)
Table 446: PHPTUV Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Num of start pha-
ses
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3
Number of phases
required for oper-
ate activation
Curve parameter A 0.005...200.000
1
1.000
Parameter A for
customer program-
mable curve
Curve parameter B 0.50...100.00
1
1.00
Parameter B for
customer program-
mable curve
Curve parameter C 0.0...1.0
1
0.0
Parameter C for
customer program-
mable curve
Curve parameter D 0.000...60.000
1
0.000
Parameter D for
customer program-
mable curve
Curve parameter E 0.000...3.000
1
1.000
Parameter E for
customer program-
mable curve
Voltage selection
1=phase-to-earth
2=phase-to-phase
2=phase-to-phase
Parameter to select
phase or phase-to-
phase voltages
Table 447: PHPTUV Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Minimum operate
time
60...60000
ms
1
60
Minimum operate
time for IDMT
curves
Reset delay time
0...60000
ms
1
20
Reset delay time
Curve Sat Relative
0.0...10.0
0.1
0.0
Tuning parameter
to avoid curve dis-
continuities
Voltage block value 0.05...1.00
xUn
0.01
0.20
Low level blocking
for undervoltage
mode
Enable block value
0=False
1=True
1=True
Enable internal
blocking
Relative hysteresis
1.0...5.0
%
0.1
4.0
Relative hysteresis
for operation
4.4.2.9
Monitored data
PHPTUV Monitored data
Table 448: PHPTUV Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start
time / operate
time
PHPTUV
Enum
1=on
Status
Protection functions
1MRS758755 C
434
REC615 & RER615
Technical Manual
Содержание Relion REC615
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...