Table 455: ROVPTOV Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
4.4.3.8
Monitored data
ROVPTOV Monitored data
Table 456: ROVPTOV Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start
time / operate
time
ROVPTOV
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.4.3.9
Technical data
Table 457: ROVPTOV Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured voltage: f
n
±2 Hz
±1.5% of the set value or ±0.002 × U
n
Start time
1
2
U
Fault
= 2 × set
Start
value
Minimum
Typical
Maximum
48 ms
51 ms
54 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
1
Residual voltage before fault = 0.0 × U
n
, f
n
= 50 Hz, residual voltage with nominal frequency in-
jected from random phase angle, results based on statistical distribution of 1000 measurements
2
Includes the delay of the signal output contact
1MRS758755 C