Table 332: EFIPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start
time / operate
time
EFIPTOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.2.1.11
Technical data
Table 333: (F)EFxPTOC Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: f
n
±2 Hz
(F)EFLPTOC
±1.5% of the set value or ±0.002 × I
n
EFHPTOC
and
EFIPTOC
±1.5% of set value or ±0.002 × I
n
(at currents in the range of 0.1…10 × I
n
)
±5.0% of the set value
(at currents in the range of 10…40 × I
n
)
Start time
1
2
Minimum
Typical
Maximum
EFIPTOC:
I
Fault
= 2 × set
Start val-
ue
I
Fault
= 10 × set
Start
value
16 ms
11 ms
19 ms
12 ms
23 ms
14 ms
EFHPTOC and (F)EFLP-
TOC:
I
Fault
= 2 × set
Start val-
ue
23 ms
26 ms
29 ms
Reset time
Typically 40 ms
Table continues on the next page
1
Measurement mode = default (depends on stage), current before fault = 0.0 × I
n
, f
n
= 50 Hz,
earth-fault current with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
2
Includes the delay of the signal output contact
Protection functions
1MRS758755 C
292
REC615 & RER615
Technical Manual