U_A
U_C
U_B
DIPST
INTST
SWELLST
Voltage Int set
Voltage dip set
Voltage swell set
FALSE
TRUE
FALSE
TRUE
FALSE
TRUE
DIPST
INTST
SWELLST
FALSE
TRUE
FALSE
TRUE
FALSE
TRUE
A) Three phase mode
B) Single phase mode
Figure 361: Detection of three-phase voltage interruption
The module measures voltage variation magnitude on each phase separately, that
is, there are phase-segregated outputs
ST_A
,
ST_B
and
ST_C
for voltage variation
indication. The configuration parameter
Phase supervision defines which voltage
phase or phases are monitored. If a voltage phase is selected to be monitored, the
function assumes it to be connected to a voltage measurement channel. In other
words, if an unconnected phase is monitored, the function falsely detects a voltage
interruption in that phase.
The maximum magnitude and depth are defined as percentage values calculated
from the difference between the reference and the measured voltage. For example,
a dip to 70 percent means that the minimum voltage dip magnitude variation is 70
percent of the reference voltage amplitude.
The activation of the
BLOCK
input resets the function and outputs.
10.3.4.3
Variation validation
The validation criterion for voltage variation is that the measured total variation
duration is between the set minimum and maximum durations (Either one of
VVa
dip time 1, VVa swell time 1 or VVa Int time 1, depending on the variation type, and
VVa Dur Max). The maximum variation duration setting is the same for all variation
types.
shows voltage dip operational regions. In
, only one voltage
dip/swell/Int set is drawn, whereas in this figure there are three sub-limits for the
dip operation. When
Voltage dip set 3 is undershot, the corresponding
ST_x
and
1MRS758755 C
Power quality measurement functions
REC615 & RER615
Technical Manual
711