In this case, the number of needed CBBs is three, that is, the first shot's
reclosing time depends on the initiation signal.
INIT_1 (I>>)
INIT_2 (I>)
INIT_3 (Io>)
Shot 1
(CBB1)
1.0s
Shot 1
(CBB2)
0.2s
Shot 2
(CBB3)
10.0s
Lockout
Lockout
Lockout
Figure 345: Three shots with three initiation lines
If the sequence is initiated from the
INIT_1
line, that is, the overcurrent
protection high stage, the sequence is one shot long. If the sequence is
initiated from the
INIT_2
or
INIT_3
lines, the sequence is two shots long.
Table 684: Settings for configuration example 2
Setting name
Setting value
Shot number CBB1
1
Init signals CBB1
1 (line 1)
First reclose time
0.0s (an example)
Shot number CBB2
1
Init signals CBB2
6 (lines 2 and 3 = 2+4 = 6)
Second reclose time
0.2s (an example)
Shot number CBB3
2
Init signals CBB3
6 (lines 2 and 3 = 2+4 = 6)
Third reclose time
10.0s
9.4.6.4
Delayed initiation lines
The auto-reclose function consists of six individual auto-reclose initiation lines
INIT_1...INIT 6
and three delayed initiation lines:
•
DEL_INIT_2
•
DEL_INIT_3
•
DEL_INIT_4
DEL_INIT_2
and
INIT_2
are connected together with an OR-gate, as are inputs 3
and 4. Inputs 1, 5 and 6 do not have any delayed input. From the auto-reclosing point
of view, it does not matter whether
INIT_x
or
DEL_INIT_x
line is used for shot
initiation or blocking.
The auto-reclose function can also open the circuit breaker from any of the initiation
lines. It is selected with the
Tripping line setting. As a default, all initiation lines
activate the
OPEN_CB
output.
Control functions
1MRS758755 C
680
REC615 & RER615
Technical Manual